HomeMy WebLinkAboutORD-38-79 SAFEGUARDING OF PERSONS AND BUILDINGS FROM HAZARDS FROM THEORANGE CITY NEWS: Please publish December 5, 1979 only and send PROOF
and PROOF OF PUBLICATION to City Clerk, P,O, Box 449, Orange, California 92666,
MARILYN J. JENSEN, CITY CLERK
ORDINANCE NO. 38-
79 AN ORDINANCE OF THE CITY COUNCIL OF THE
CITY OF ORANGE ADOPTING, BY REFERENCE, THE
NATIONAL ELECTRICAL CODE, 1978 EDITION, AND
APPENDIX,PROVIDING FOR A PRACTICAL METHOD FOR
THE SAFEGUARDING OF PERSONS AND OF BUILDINGS
AND THEIR CONTENTS FROM HAZARDS ARISING FROM
THE USE OF ELECTRICITY FOR LIGHT, HEAT,
POWER,RADIO, SIGNALING AND OTHER PURPOSES, AND
WITH CERTAIN AMENDMENTS, AND FIXING PENALTIES
FOR
VIOLATION.THE CITY COUNCIL OF THE CITY OF ORANGE DOES ORDAIN
AS
FOLLOWS:SECTION
I:Chapter 3, Part I, containing Sections 8300 through 8302
of the Orange Municipal Code are amended to read as
follows:Adoption of the National Electrical
Code,1978 Edition, and
Appendix.The National Electrical Code, 1978 Edition, and
Appendix,published by the National Fire Protection with the
additions,changes, and deletions set forth in Section 8301 of
the Orange Municipal Code are adopted by reference. The
required copies are on file in the office of the City Clerk for
use and examination by the
public.Section
8300 Section 8301 Modification of the National Electrical
Code,1978
Edition.The National Electrical Code, 1978 Edition, is adopted with
the following additions, changes and
deletions:ARTICLE 110 - - REQUIREMENTS FOR ELECTRICAL INS
TALLATIONS Section
110-5 is amended by adding the following paragraph
to read as follows:
Section 110-5 Conductors. No aluminum conductor
smaller than No.6 AWG shall be
used.ARTICLE 210 - - BRANCH CIRCUITS Section
210-1 is amended to read as follows:
Section 210-1 Scope. The provisions of this Article
apply to branch circuits supplying lighting or appliance loads
or combinations of such loads. Where motors, or
motor-operated appliances, are connected to any circuit
supplying lighting or other appliance loads, the provisions of both
this Article and Article 430 shall apply. Article 430 shall
apply where branch circuit supplies only
a. Accessory uses or other buildings, signs, etc.,
separately located on the same lot or premises shall
have connecting conductors run underground. (Agricultural
areas excepted.)
b. Where space circuit protective devices are provided or
space for future circuit protective devices is provided
on the buss in any flush or semi-flush mounted
panel,then raceways of sufficient capacity to permit
utilization of such spaces or spaces shall be provided to an
approved accessible location. Such accessible location
is normally defined as
follows:Where sufficient attic space is available
or underf100r space is available, a raceway
shall terminate conveniently for future use in each
such space. Where this condition does not exist,
then such terminations shall be approved by the
enforcing
authority.The last sentence of Section 2l0-25(b) on
Page 70-36 is amended to
read as follows:For a one-family dwelling,
at least one receptacle outlet, in addition to any
provided for laundry equipment,shall be installed in each
basement, garage, and carport.Garages or carports adjacent to
dwelling units shall be wired with a minimum of one
switched light outlet and one receptacle per each two
auto stalls or fraction thereof. This wiring, if exposed,
shall be in approved metal raceways. All
wiring to detached accessory buildings
shall be run underground.No convenience receptacle
or appliance receptacle shall be installed or operated on
a general lighting branch circuit at any
time in any occupancy.The first two paragraphs of section
210-26(a) are deleted and
the following four paragraphs added:
Section 210-26 Liqhting Outlets Required.a.1.
Dwelling-Type Occupancies: At least one wal1-
switch controlled lighting outlet shall be installed
in every habitable room; in hallways,
stairways,garages, carports, and at outdoor entrances.2.
All Occupancies: At least one lighting outlet
shall be installed in attic, underf100r space,utility
area and basement where used for
storage or containing equipment requiring servicing, and at
ingress or egress of commercial type buildings.
3. Area Lighting: Every multiple dwelling complex shall be
illuminated with not less than one foot-candle at
floor or ground level along walkways to a
public way. This lighting shall
be provided continuously from sun-down to sun-
up.4. Area Lighting - Commercial and Industrial
Complexes and Parking Areas: Sufficient lighting shall be
provided
ARTICLE 230 - - SERVICES Section 230-
43 is amended to read as follows:Section
230-43 Wiring Methods for 600 Volts or Less.
Service entrance conductors extending along the exterior or
entering buildings or other structures shall be enclosed in
rigid metal conduit to the first over-current device, or
for circuits not exceeding 600 volts in wire ways
auxiliary gutters or as busways. (Overhead
services.)Section 230-7l(a) is amended to read
as follows:section 230-7l(a) Disconnection
from Service Conductors.A single fusible switch or automatic
circuit breaker shall be provided to disconnect all
ungrounded conductors supplying
each separately-metered occupancy.ARTICLE 300 - -
WIRING METHODS Section 300-15(b) is amended by
deleting Exceptions No.1
and No.5.ARTICLE 336 - - NON-METALLIC
SHEATHED CABLE The first paragraph of Section 336-3 is
amended to
read as follows:Section 336-3 Uses Permitted
or not Permitted. Non-metallic sheathed cable shall not be
used for exposed wiring and shall only be used for concealed
wiring in one and two family dwellings
or multi-family dwellings (apartment houses)
not exceeding three floors above grade.Article 336 is amended
by
deleting Section 336-6 in its entirety.
ARTICLE 350 - - FLEXIBLE METAL CONDUIT Section 350-2
is amended by adding Subsection (
7)to read as fo 110ws :
7. Where exposed to physical
damage.ARTICLE 422 - - APPLIANCES Section 422-5 is amended
by adding paragraph (
c) to read as follows:
Section 422-5 Branch Circuit Sizing.c) Fixed Appliances:
Each dwelling unit shall have installed therein an
individual food waste grinder branch circuit.said circuit shall be
supplied with a 15 ampere indicating-type switch. Said switch
shall be located in the wall adjacent to the sink.
A food waste grinder shall be wired with a minimum
of No. 16 AWG, 3-wire SPT-3 thermoplastic
hard finish cord or its equal and an approved
grounding
Section 8302 Violations and Penalties.
Any person, firm or corporation violating any of the provl.sl.ons
of this Code shall be deemed guilty of a misdemeanor, and
each such person shall be deemed guilty of a separate offense
for each and every day or portion thereof during which any
violation of any of the provisions of this Code is committed,
continued, or permitted, and upon conviction of any such
violation such person shall be punishable by a fine of not
more than $500.00, or by imprisonment for not more than six
months, or by both such fine and imprisonment.
In addition, this Code may be enforced by injunction or
appropriate civil remedy.
SECTION II:
This ordinance shall be published once within fifteen (15)
days after its passage in the Orange City News, a newspaper of
general circulation, published and circulated in the City of
Orange, and shall take effect thirty (30) days from and after
the date of its final passage.
ADOPTED this 27th day of November, 1979.
1..t...;)r \.0 -"t -"r-Mayor of
the City of Orange ATTEST:of
Orange
STATE OF
CALIFORNIA )COUNTY OF
ORANGE ) ss CITY OF
ORANGE )I, !1ARILYN
J. JENSEN, City Clerk of the City of Orange,California, DO
HEREBY CERTIFY that the foregoing ordinance was introduced at
a regular meeting of the City Council duly held on the 20th
day of November, 1979, and thereafter at a regular meeting of
said City Council duly held on the 27th day of November, 1979,
was duly passed and adopted by the following vote, to
wi t :AYES:NOES:
ABSTAINED:
ABSENT:
BARRERA,
SMITH,
MAYOR HOYT, PEREZ NONE BEAM
NONE
COUNCILMEN:
COUNCILMEN:
COUNCILMEN:
COUNCILMEN:
WITNESS
my
hand and seal this 28th day of November, 1979.7'lcti~(.
4.
r.r'" ,YMarilyn
J. Jensen
City Clerk of
the f~' ,L-t... /~
Ci ty of
Orange 4-